6 Unison® ERn Rack Mount Enclosure Installation ManualPreparationsUnpack and InspectBefore you begin installation, check your shipment and confirm it
1 Prepare for Installation 7• Let others know that the equipment is back in service. Maximum Current InputThe ERn enclosure draws a maximum current of
8 Unison® ERn Rack Mount Enclosure Installation ManualRack Mounting SpecificationsAn ERn configured for installation in a 19” equipment rack requires
1 Prepare for Installation 9Wire RequirementsWire Routing and SpecificationThe rear panel of the Unison® ERn rack mount unit includes a full complimen
10 Unison® ERn Rack Mount Enclosure Installation ManualThe following table lists the recommended control wire types used in a typical Unison ERn insta
2 Install Enclosure 11Chapter 2Install EnclosureThis chapter contains instructions for installation of the ERn enclosure.The introduction contains the
12 Unison® ERn Rack Mount Enclosure Installation ManualInstall in a 19” Equipment RackRack mounting brackets are installed on the ERn unit when shippe
3 Connect Wiring 13Chapter 3Connect WiringThis chapter contains the following sections:• IEC Power Input Connector . . . . . . . . . . . . . . . . .
14 Unison® ERn Rack Mount Enclosure Installation ManualIEC Power Input ConnectorERn Rack Mount Enclosure Power InputThe ERn enclosures are available i
3 Connect Wiring 15Connect Control WiringAll low voltage data and option wiring conveniently connects to removable and pluggable connectors on rear pa
ETC®, Unison®, EDMX™ are either registered trademarks or trademarks of Electronic Theatre Controls, Inc. in the United States and other countries.Eche
16 Unison® ERn Rack Mount Enclosure Installation ManualDMX Input/Output Termination: Insulation Displacement ConnectorsThe graphic below illustrates D
3 Connect Wiring 17Step 3: Remove the LinkPower connector (labeled LON).• Notice the LinkPower/LON connector is labeled to indicate that the connector
18 Unison® ERn Rack Mount Enclosure Installation ManualStatus IndicatorsWhen power is applied to the ERn enclosure, the Paradigm repeater module LEDs
3 Connect Wiring 19Connect to Contact Inputs and Contact OutputsThe rear panel I/O provides convenient interface (inputs and outputs) to external devi
20 Unison® ERn Rack Mount Enclosure Installation ManualRight I/O Board TerminationsThe right I/O board is located inside the ERn enclosure and serves
4 Install Rack Options 21Chapter 4Install Rack OptionsThis chapter contains the following sections:• Install the Ride Thru Option (URTO) Kit . . . .
22 Unison® ERn Rack Mount Enclosure Installation ManualRack OptionsUnison ERn rack mount unit options include the ride through option (URTO) kit and t
4 Install Rack Options 23Step 2: Align the ride through option board to the mounting studs in the right corner of the ERn enclosure (see graphic on th
24 Unison® ERn Rack Mount Enclosure Installation ManualInstall a Paradigm Repeater or Dual Repeater ModuleThe Paradigm station repeater (P-REP) module
4 Install Rack Options 25Terminate LinkPower (LON®) Control WiringUnison control stations communicate with the Paradigm architectural control processo
Table of Contents iTable of ContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . 1ERn Modules and Options. . . . . . . . . . . . .
26 Unison® ERn Rack Mount Enclosure Installation Manualthe connector provided. Reference the related station installation manual for further details.S
4 Install Rack Options 27Status IndicatorsWhen power is applied to the ERn enclosure, the Paradigm repeater module LEDs located on the front panel ill
28 Unison® ERn Rack Mount Enclosure Installation ManualInstall Redundant Power SupplyThe ERn redundant power supply (ERn-RPS) is an additional rack po
5 Final Installation and Power Up 29Chapter 5Final Installation and Power UpThis chapter contains the following sections:• Check Main Power Wiring . .
30 Unison® ERn Rack Mount Enclosure Installation ManualCompleting the InstallationIt’s a good idea to look over the entire installation before applyin
5 Final Installation and Power Up 31Final InstallationStep 1: Install the Paradigm architectural control processor (P-ACP) in the appropriate module s
Corporate Headquarters 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel +608 831 4116 Fax +608 836 1736London,
ii Unison® ERn Rack Mount Enclosure Installation ManualInstall Rack Options . . . . . . . . . . . . . . . . . . 21Rack Options . . . . . . . . . . .
Introduction 1IntroductionWelcome to the installation manual for the Unison® ERn rack mount external processing enclosure. This manual contains the pr
2 Unison® ERn Rack Mount Enclosure Installation ManualERn Modules and OptionsModelPart NumberDescription NotesP ACP 7180A1001 Paradigm Architectural C
Introduction 3URTO 7180A1410 Unison Ride Thru Option KitThe URTO kit provides power for one Paradigm architectural control processor in the host enclo
4 Unison® ERn Rack Mount Enclosure Installation ManualWarnings and Notice ConventionsThese symbols are used in ETC documentation to alert you to dange
1 Prepare for Installation 5Chapter 1Prepare for InstallationThis chapter contains the following sections:• Preparations . . . . . . . . . . . . . . .