Sensor3 CE Rack (ESR3 Series)Installation ManualRevision FCopyright © Electronic Theatre Controls, Inc.All rights reserved.Product information and spe
2 Sensor3 CE Rack (ESR3) Installation ManualContacting ETCIf you are having difficulties, your most convenient resources are provided in this installa
1 Prepare for Installation 3Chapter 1Prepare for InstallationUnpack and InspectBefore you begin installation, check your shipment and confirm it arriv
4 Sensor3 CE Rack (ESR3) Installation Manual.Where to Mount the RackSensor3 dimmer racks require 25cm of top clearance for proper airflow through the
2 Installation of Racks 5Chapter 2Installation of RacksMounting the Rack• ESR3-12 racks are normally wall-mounted.• ESR3-24 racks can be mounted to a
6 Sensor3 CE Rack (ESR3) Installation ManualInstalling ESR3-36 and ESR3-48 Racks on the FloorStep 1: Determine where your rack will be installed using
2 Installation of Racks 7Securing Sensor3 Racks to a Wall Racks installed on the floor or a pedestal can also be secured to a wall for greater stabili
8 Sensor3 CE Rack (ESR3) Installation ManualWall Mounting Racks Using Vibration PadsVibration damping fittings are available as an option for wall mou
2 Installation of Racks 9to the floor on page 7 to mark your hole locations.Step 3: Align the center of the vibration fitting over the hole locations
10 Sensor3 CE Rack (ESR3) Installation ManualSecuring Multiple Racks (Optional)Multiple racks can be connected to each other for greater stability.Ste
2 Installation of Racks 11Rack Cabling AccessESR3 racks have removable top and bottom access panels.Conduit ConnectionsStep 1: Remove the desired acce
ETC permits the reproduction of materials in this manual only for non-commercial purposes. All other rights are reserved by ETC.ETC® and Sensor® are e
12 Sensor3 CE Rack (ESR3) Installation ManualConnect Line Power WiringETC recommends routing line (feeder) cables first, load neutral and load earth w
3 Land Load Wires 13Chapter 3Land Load WiresLand Load WiresEach dimmer has three sets of lugs connected to phase, neutral and earth. Phase and earth l
14 Sensor3 CE Rack (ESR3) Installation Manualthat phase, neutral and earth can be corrected to the relevant lugs as shown.Step 3: Fit load earth wires
3 Land Load Wires 15Cut Key Slots for ModulesSensor3 dimming and control modules are easily slid into place by hand. Each module slot is keyed to acce
16 Sensor3 CE Rack (ESR3) Installation ManualConverting Neutral Disconnect SlotsThere are two classes of modules available for Sensor3 CE racks - modu
3 Land Load Wires 17Installing Three-Slot Dimmer Lug StripsStep 1: Use a Phillips screwdriver to remove the two screws securing the lug strip to the l
18 Sensor3 CE Rack (ESR3) Installation Manual
4 Control and Data Connections 19Chapter 4Control and Data ConnectionsSensor3 racks support a variety of control and data connections on the CEM3 back
20 Sensor3 CE Rack (ESR3) Installation ManualRunning DMX Cable to RacksStep 1: Remove the desired top, bottom or side conduit knockout from the first
4 Control and Data Connections 21with the rack and should be ordered separately.Step 2: If needed, terminate both the outgoing cables into the third h
iTable of ContentsWarnings. . . . . . . . . . . . . . . . . . . . . . . iiiIntroduction . . . . . . . . . . . . . . . . . . . . . .1How to use this G
22 Sensor3 CE Rack (ESR3) Installation ManualRunning Ethernet to RacksSensor3 racks use Ethernet for communication with each other and sometimes for c
4 Control and Data Connections 23Ethernet Network Termination - RJ45 ConnectorStep 1: Follow the directions provided in the Ethernet Termination Kit t
24 Sensor3 CE Rack (ESR3) Installation ManualDual Tracking Remote Select Switch connection (Optional)If desired, a remote switch can be wired to the C
4 Control and Data Connections 25Station Connection (Optional)Sensor3 racks support ETC’s range of stations. The station network should be wired in Be
26 Sensor3 CE Rack (ESR3) Installation Manual
5 Finishing Installation 27Chapter 5Finishing InstallationThe steps in this chapter should only be performed by, or after receiving approval from, an
28 Sensor3 CE Rack (ESR3) Installation ManualSensor3 Installation ChecklistA checklist is provided in Appendix B: Sensor3 Installation Checklist, page
5 Finishing Installation 29with two Phillips head screws (included).Figure 28: Attaching the top door hingeStep 2: The bottom hinge on the ESR3-12 is
30 Sensor3 CE Rack (ESR3) Installation Manualtaper pin through the washers and into the hole on the lower hinge. Figure 31: Installing the bottom tape
5 Finishing Installation 31Checking Rack Installation before Installing ModulesIt is a good idea to check the installation before applying power to th
ii Sensor3 CE Rack (ESR3) Installation ManualEthernet Network Termination - RJ45 Connector. . . . . 23Panic Circuit Connections (Optional) . . . . .
32 Sensor3 CE Rack (ESR3) Installation ManualInstalling Dimmer ModulesStep 1: Inspect each dimmer module for loosened components or shipping damage.St
5 Finishing Installation 33Testing an Installed Sensor3 RackAfter finishing installation, use this procedure to perform a functional check.Step 1: Mak
34 Sensor3 CE Rack (ESR3) Installation ManualAppendix ASensor3 CE Rack SpecificationsAll of the rack specifications apply to all of the ESR3 series of
B Sensor3 Installation Checklist 35Appendix BSensor3 Installation ChecklistPlace a tick in each box to confirm item has been checked and is OK. Write
36 Sensor3 CE Rack (ESR3) Installation ManualAppendix CEmergency ModulesAbout Emergency ModulesSensor3 CE Emergency modules provide two live outputs,
C Emergency Modules 37Step 5: Terminate the neutral as described below dependant on your rack type.Single Pole RacksFor racks which have neutral jumpe
Corporate Headquarters 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel +608 831 4116 Fax +608 836 1736London,
Warnings iiiWarningsWARNING:(GB)• INCORRECT CONNECTION MAY CAUSE DAMAGE OR INJURY.• FOR PROFESSIONAL USE ONLY.• THIS EQUIPMENT MUST ONLY BE CONNECTED
iv Sensor3 CE Rack (ESR3) Installation ManualVAROITUS:(FI)• KYTKENTÄVIRHE VOI AIHEUTTAA LAITTEEN RIKKOUTUMISEN TAI HENGENVAARAN.• VAIN AMMATTIKÄYTTÖÖ
Warnings vWAARSCHUWING:(NL)• VERKEERD AANSLUITEN KAN RESULTEREN IN SCHADE OF LETSEL.• ALLEEN VOOR PROFESIONEEL GEBRUIK.• DEZE APPARATUUR MAG ALLEEN DO
vi Sensor3 CE Rack (ESR3) Installation ManualDIKKAT:(TR)• YANLIŞ BAĞLANTI, HASAR VEYA YARALANMALARA SEBEP OLABİLİR.• YALNIZCA PROFESYONEL KULLANIM İÇİ
Introduction 1IntroductionWelcome to the installation manual for Sensor®3 CE racks. This manual contains the procedures for safe and efficient install